Estimados leitores e amigos, aqui mais uma página onde poderão desfrutar de uma completa nomeclatura e caderno de encargos sobre instalações electricas e alguns links que vos direcionarão a sites bem interessantes onde os cálculos e conversões são o tema principal !
DIVIRTAM-SE
Comprimentos e distâncias Construçao
Potências Ecal-apoio matemático
| GUIDELINES ON | |
Energy Efficiency of Electrical Installations
|
![]() |
| 4. Energy Efficiency Requirements for power distribution in buildings | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
| 4.1 High Voltage Distribution | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
The Code requires that high voltage (HV) distribution systems should be employed for high-rise buildings to suit the load centers at various locations. A high-rise building is defined as a building having more than 50 storeys or over 175m in height above ground level.The number of modern air-conditioned high-rise office buildings in Hong Kong is increasing rapidly during the past decade. Following the release of height restriction in certain areas after the opening of the new Hong Kong International Airport at Chek Lap Kok in 1998, it is expected that the growth of high-rise buildings will continue to boom. | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
| 4.2 Minimum Transformer Efficiency | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
The Code requires that the privately owned distribution transformers should be selected to optimise the combination of no-load, part-load and full-load losses without compromising operational and reliability requirements of the electrical system. The transformer should be tested in accordance with relevant IEC standards and should have a minimum efficiency shown in Table 4.1 at the test conditions of full load, free of harmonics and at unity power factor. Table 4.1: Minimum Transformer Efficiency | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
| 4.3 Locations of Distribution Transformers and Main LV Switchboard | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
The Code requires that the locations of distribution transformers and main LV switchboards shall preferably be sited at their load centres rather than at the periphery of the buildings, provided that all local supply rules and fire regulations etc. could also be complied.Traditional location of a transformer room in a building is normally at the ground floor level with an appropriate vehicular access for loading and unloading substation equipment. The main LV switchroom is normally located adjacent to the transformer room and all sub-main and feeder circuits including the rising mains will be fed from the main LV switchboard. Distribution losses and cost for electrical loads at roof level and far away from the main LV switchboard are usually high. | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
| 4.4 Main Circuits | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
The Code requires that the copper loss of every main circuit connecting the distribution transformer and the main incoming circuit breaker of a LV switchboard should be minimised by means of either: | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
| 4.5 Feeder Circuits | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
A feeder circuit is defined as a circuit connected directly from the main LV switchboard to the major current-using equipment such as chiller plant, pump sets and lift system. The code requires that the maximum copper loss in every feeder circuit should not exceed 2.5% of the total active power transmitted along the circuit conductors at rated circuit current. This requirement does not apply to circuits used for compensation of reactive and distortion power. For a 3-phase circuit with balanced and linear load, the apparent power transmitted along the circuit conductors in VA is: | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
| 4.6 Sub-main Circuits | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
A sub-main circuit can be defined as a circuit connected directly from the main LV switchboard to a sub-main distribution panel or a rising main for final connection of the minor current-using equipment. The Code requires that the maximum copper loss in every sub-main circuit should not exceed 1.5% of the total active power transmitted along the circuit conductors at rated circuit current.Similar approach could be followed for sizing conductor as feeder circuit above. However, assumption has to be made in the design for various characteristics of the sub-main circuit including design current, expected harmonic current (THD) in the circuit, degree of unbalance, etc. Fundamental current, I1 = 100A | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
| 4.7 Final Circuits | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
A final circuit is defined as a circuit connected directly from a sub-main panel (distribution board ) to current using equipment, or to a socket-outlet or socket-outlets or other outlet points for the connection of such equipment. The Code requires that the maximum copper loss for every single-phase or three-phase final circuit over 32A should not exceed 1% of the total active power transmitted along the circuit conductors at rated circuit current.This requirement excludes most standard final circuits below 32A rating for lighting, socket outlet and small power distribution in buildings in which minimum conductor size is specified in the Electricity (Wiring) Regulation. However, designers are required to ensure that the standard final circuits (A1 ring, A2 radial and A3 radial) using 13A socket outlets, as slated in Clause 6C of the Code of Practice for the Electricity (Wiring) Regulations, should be as short as possible by locating the MCB distribution board at the proximity of the areas served by the circuit. | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
| 6. ENERGY EFFICIENCY REQUIREMENT FOR POWER QUALITY | ||||||||||||
| 6.1 Maximum Total Harmonic Distortion (THD) of Current on LV Circuits | ||||||||||||
The total harmonic distortion (THD) of current for any circuit should not exceed the appropriate figures in Table 6.1. According lo the quantity and nature of the known non-linear equipment to be installed in the building, design calculations are required to demonstrate sufficient provision of appropriate harmonic reduction devices to restrict harmonic currents of the non-linear loads at the harmonic sources, such that the maximum THD of circuit currents, at rated load conditions, shall be limited to those figures as shown in Table 6.1 below.Table 6.1: Maximum THD of current in percentage of fundamental | ||||||||||||
| 6.2 Balancing of Single-phase Loads | ||||||||||||
All single-phase loads, especially those with non-linear characteristics, in an electrical installation with a three-phase supply should be evenly and reasonably distributed among the phases. Such provisions are required to be demonstrated in the design for all three-phase 4-wire circuits exceeding 100A with single-phase loads.The maximum unbalanced single-phase loads distribution, in term of percentage current unbalance shall not exceed 10%. The percentage current unbalance can be determined by the following expression: |
| 7. REQUIREMENTS FOR METERING AND MONITORING FACILITIES |
| 7.1 Main Circuits |
The Code requires that all main incoming circuits exceeding 400A (3-phase 380V) current rating should be incorporated with metering devices, or provisions for the ready connection of such devices, for measuring voltages (all phase-to-phase and phase-to-neutral), currents (all lines and neutral currents) and power factor, and for recording total energy consumption (kWh) and maximum demand (kVA). |
| 7.2 Sub-main and Feeder Circuits |
The Code requires that all sub-main distribution and individual feeder circuits exceeding 200A (3-phase 380V) current rating should be complete with metering devices, or provisions for the ready connection of such devices, to measure currents (3 phases and neutral) and record energy consumption in kWh for energy monitoring and audit purposes. This requirement does not apply to circuits used for compensation of reactive and distortion power.The advanced power-monitoring instrument available nowadays can be used for metering, power quality analysis, energy management and supervisory control for power distribution systems. In these digital meters, true waveforms of all voltages and currents are sampled and computations are carried out by built-in microprocessors to take into account of all the distortions associated with both currents and voltages. In this case, the true total power factor, true active power and voltages and currents in true r.m.s. values can be obtained. The instrument can also be linked into the building management system of the building as one element in an energy management network. Selection for applying the most beneficial tariff system could also be analysed by the instrument from the logged data of energy consumption and load profile of the building. |
| 8. |
| 8.1 Emergency Maintenance |
The emergency maintenance can hardly be regarded as maintenance in the sense that, in many cases, it consists of an urgent repair to, or replacement of, electrical equipment that has ceased to function effectively. Obviously, it is better to follow a rigorous 'Planned Maintenance Programme' for all essential electrical power distribution installations and equipment in buildings to reduce the frequency of emergency maintenance tasks. |
| 8.2 Planned Maintenance |
In the use of electrical plant and equipment there are obviously sources of danger recognised in the 1990 Electricity (Wiring) Regulations. These regulations are mandatory and serve to ensure that all electrical plants and equipment are adequately maintained and tested to prevent any dangerous situation arising that could harm the users of such equipment or the building occupants. Normally, maintenance carried out solely for safety reasons will be covered by standard procedures, which in some instances will have to fulfill the relevant Code of Practice for the Electricity (Wiring) Regulations. For example, Code 20 'Periodic Inspection, Testing and Certification', Code 21 'Procedures for Inspection, Testing and Certification' and Code 22 'Making and Keeping of Records'. As these types of maintenance work are solely legislative requirements it is not proposed to discuss here on economic considerations. Planned maintenance can be carried out on the basis of the operation of the piece of electrical equipment itself. For example, it is worth considering whether all electric motors should be periodically cleaned and inspected, making sure that dirt and dust has not interfered with the self cooling of the motor and that there is no oil leakage into the motor's windings. Bearing should also be checked for wear and tear to prevent contact between the rotor and stator. Maintenance can also be based on the complete item of plant, or auxiliary plant, such as the central air conditioning plant of a tall building. |
| 8.3 Purpose of Maintenance |
Apart from safety, maintenance is needed to keep plant in an acceptable condition. Maintenance of this kind must be reviewed on an economic and energy efficiency basis. While it is appreciated that breakdown of plant may result in costly interruption of normal building operation, it must also be borne in mind that stopping plant for maintenance can also cause a loss in production. Equipment on continuous and arduous duty, e.g. switchboards, motor control centres, air-handling units, chiller plant etc., require more attention than that which is lightly loaded and rarely used. |
| 8.4 Economic and Energy Efficiency of Maintenance |
Apart from the above considerations there will be the question of whether to repair or replace faulty equipment. This requires analysis of the past and future maintenance costs and the benefits of new equipment. There has been much operational research carried out into such things as the probability of breakdown, replacement and repair limits, and overhaul policies. This obviously requires considerable effort and expertise and may need the services of a specialist consultant. However, some simple initial steps can be taken as far as the economic and energy efficiency is concerned for maintenance of electrical equipment in buildings. 8.4.1 Standardisation of Equipment |
ALL DATAS , CALCULATIONS , DESCRIPTIONS AND CONCEPTS, ARE BASED ON STANDARDS REGULATIONS OF LAW IN DIFF.COUNTRIES OF EUROPE, ASIA AND THE UNITED STATES.FOR ANALYSIS THE BEST WAY OF THE DATA DESCRIBED THE BASIS AND CONCERNING REGULATIONS ARE FOM HONG KONG, THAT ARE SIMILAR TO MOST EUROPEAN COUNTRIES. TO MAKE OTHER CALCULATIONS CAN BE USED THE BASIS OF EXAMPLES AS MENTIONED IN THE TEXT.
TODOS OS DADOS, CALCULOS, CONCEITOS E DESCRIÇOES FORAM BASEADOS EM NORMAS REGULARES VIGENTES NA LEI DE DIVERSOS PAÍSES DA EUROPA, ASIA E ESTADOS UNIDOS. PARA MELHOR ANÁLISE SOBRE OS DADOS DESCRITOS, A BASE DE FUNDO É REFERENTE AS NORMAS VIGENTES EM HONG KONG QUE SAO SIMILARES À MAIORIA DOS PAÍSES EUROPEUS. PARA REALIZAR OUTROS CALCULOS PODERÁ SERVIR-SE DE BASE OS EXEMPLOS MENCIONADOS NO TEXTO.

A pen USB DataTraveler I G3 da Kingston oferece uma capacidade de armazenamento de 4 GB para guardar os seus dados. Fiável e prática, a pen USB DataTraveler de terceira geração da Kingston é a solução ideal para armazenar e transportar para todo o lado as suas fotografias, vídeos, músicas e conteúdos multimédia. A pen possui uma argola traseira onde pode fixar um fio para facilitar o transporte.

O disco rígido externo WD Elements Desktop é uma solução de armazenamento perfeitamente concebida para armazenar e partilhar ficheiros. Graças a uma capacidade interna de 2 TB, o disco rígido Elements Desktop pode receber os seus ficheiros áudio, vídeo e de imagem. A sua ligação USB 2.0 oferece uma taxa de transferência de dados elevada e uma utilização inteiramente Plug & Play. O disco rígido externo WD Elements Desktop é uma unidade de armazenamento eficiente para todos os seus dados.

Compatível com o Windows e Mac, a pen USB Lexar JumpDrive V10 armazena todos os seus dados para os ter num local seguro.

O disco rígido Seagate Momentus 5400.6 160 GB armazena todos os seus dados, sendo dotado de uma memória buffer de 8 MB. Concebido para os computadores portáteis, o disco rígido Momentus 5400.6 160 GB distingue-se pela sua fiabilidade e rapidez em todas as circunstâncias, através da tecnologia G-Force que reforça a resistência aos choques.

Prático e eficaz, o disco rígido externo portátil Seagate Expansion 500 GB pode receber os seus dados áudio, vídeo e documentos facilmente, com uma taxa de transferência de até 480 Mbits por segundo! Plug & Play, este disco rígido externo 2,5" Expansion da Seagate não precisa de alimentação externa e possui a vantagem de ser muito silencioso.

Ideal para os computadores de jogos ou estações de trabalho, o disco rígido Seagate Barracuda 7200.12 1 TB distingue-se pela sua fiabilidade e rapidez.

Com uma capacidade de 4 GB, a pen USB Cruzer Blade da SanDisk permite-lhe transportar facilmente as suas imagens, vídeos, músicas e documentos pessoais!

Aumente a capacidade de armazenamento do seu computador com o Seagate Barracuda Green de 2 TB! Económico em energia, este disco rígido Barracuda Green da Seagate possui uma interface SATA III, ou seja, 6 Gbps, e uma memória cache de 64 MB para obter uma velocidade de execução impressionante!

Compatível com Windows e Mac, esta pen USB Lexar JumpDrive V10 armazena todos os seus dados de forma segura e fiável.

Ofereça uma Sapphire Radeon HD 6950 ao seu PC! Ideal para os jogadores e utilizadores de PC avançados, a placa gráfica Radeon HD6950 da Sapphire possui as tecnologias de aceleração visual AMD EyeSpeed e AMD HD3D. A placa Radeon HD 6950 é indicada para os jogos de alta gama para beneficiar de uma experiência HD inesquecível. Compatível com DirectX 11, oferece-lhe uma taxa de imagens por segundo extraordinária. Quanto à tecnologia AMD Eyefinity, permite-lhe aumentar o seu campo de visão até 6 monitores em simultâneo! Perfeita igualmente para a leitura de vídeos em HD e montagem de vídeos, a placa gráfica HD 6950 da Sapphire est é indispensável para o seu computador.

O Core i7 é um processador da Intel que pertence a uma geração de processadores de alta performance! Dedicado ao overclocking e com 3,4 GHz, o Intel Core i7 2600K integra a tecnologia Hyper-Threading para ganhar até 40% de performance. Ideal para todas as aplicações executadas em simultâneo, o processador Core i7 2600K da Intel possui um chipset gráfico HD, assim como um modo Turbo para explorar ao máximo os seus quatro núcleos.

Optimize a abertura das suas aplicações com o kit de 2 barras de 4 GB de memória RAM Corsair Vengeance Performance, ou seja, 8 GB no total! Graças à norma DDR3 de 1600 MHz, poderá oferecer uma elevada performance às suas aplicações multimédia ou jogos de vídeo. Concebido para os utilizadores mais exigentes, o kit Vengeance Performance da Corsair fornece velocidade, fiabilidade e estabilidade ao seu computador.

A pen USB Emtec C400 possui um design moderno e colorido. Dotada de uma capacidade de 4 GB, a pen C400 da Emtec armazena todos os seus dados para levar para todo o lado. Além disso, pode fixar a tampa da pen atrás durante a sua utilização.

Facilmente transportável, a DataTraveler 100 G2 da Kingston é uma pen USB 2.0 leve e fiável para armazenar os seus dados. Compatível com Windows, Mac e Linux, a DataTraveler 100 Generation 2 não necessita de instalação prévia para funcionar.

Ideal para os computadores de jogos ou estações de trabalho, o disco rígido Seagate Barracuda 7200.12 500 GB distingue-se pela sua fiabilidade e rapidez.





























APPLE



